Catalog navigation
All catalogs
Geometric Search
CAD model selection
Add for comparison
Selectable products: 1
Company
ABB Low Voltage & Systems
Description
Vital1 - Safety controller
Bill of material
ABB - 2TLA020052R1000 + Vital 1 Safety controller 2NO, +24 VDC
Product ID
2TLA020052R1000
Extended Product Type
Vital 1
Invoice Description
Vital 1 Safety controller 2NO, +24 VDC
Description
Safety module with one single channel input for dynamic sensors. Relay outputs 2NO.
Long Description
Vital 1 Safety controller with relay outputs 2NO, +24 VDC supply voltage and detachable screw terminals. For monitoring of safety devices, such as emergency stops, using DYNlink. Vital 1 is a configurable safety controller that does not require programming. It uses the DYNlink system, which allows up to 30 safety devices to be connected in series to the same circuit, while achieving PL e / SIL 3. The DYNlink circuit is a unique solution that uses one single channel to achieve upt to Cat.4/PL e. Using DYNlink reduces the installation and engineering time thanks to simple installation with serial connection using M12 connectors. Vital 1 can only be used with DYNlink safety devices, such as Eden DYN and devices with a Tina adapter.
International product number
7350024431810
Product number of the Manufacturer
2TLA020052R1000
Model
Other
Suitable for monitoring of position switches
true
Suitable for monitoring of emergency-stop circuits
true
Suitable for monitoring of valves
true
Suitable for monitoring of optoelectronic protection equipment
true
Suitable for monitoring of tactile sensors
false
Suitable for monitoring of magnetic switches
true
Suitable for monitoring of proximity switches
true
Type of electric connection
Screw connection
Rail mounting possible
true
Rated control supply voltage Us at AC 50HZ
- - - V
Rated control supply voltage Us at AC 60HZ
- - - V
Rated control supply voltage Us at DC
24 - 24 V
Voltage type for actuating
DC
With detachable clamps
true
Evaluation inputs
1-channel
With start input
true
With muting function
false
With feedback circuit
true
Release-delay
48 - 48 s
Number of outputs, safety related, undelayed, with contact
2
Number of outputs, safety related, delayed, with contact
0
Number of outputs, safety related, undelayed, semiconductors
0
Number of outputs, safety related, delayed, semiconductors
0
Number of outputs, signalling function, undelayed, with contact
0
Number of outputs, signalling function, delayed, with contact
0
Number of outputs, signalling function, undelayed, semiconductors
0
Number of outputs, signalling function, delayed, semiconductors
0
Type of safety according to IEC 61496-1
4
Stop category according to IEC 60204
0
Performance level according to EN ISO 13849-1
Level e
SIL according to IEC 61508
3
With approval for BG BIA
false
With approval according to UL
false
Width
22.5 mm
Height
84 mm
Depth
120 mm
With approval for TÜV
true
Customs tariff number
85364900
Deeplink product page
Link to product detail page
Type
Vital 1
Procurement
Last updateDec 10, 2025, 10:55 AM
Part number2TLA020052R1000
All information without guarantee
Last update: Dec 10, 2025, 10:55 AM
Preview - Generation
Preview
3D
2D

Classifications
CNS
Object Properties:
Description long: Vital 1 Safety controller with relay outputs 2NO, +24 VDC supply voltage and detachable screw terminals. For monitoring of safety devices, such as emergency stops, using DYNlink. Vital 1 is a configurable safety controller that does not require programming. It uses the DYNlink system, which allows up to 30 safety devices to be connected in series to the same circuit, while achieving PL e / SIL 3. The DYNlink circuit is a unique solution that uses one single channel to achieve upt to Cat.4/PL e. Using DYNlink reduces the installation and engineering time thanks to simple installation with serial connection using M12 connectors. Vital 1 can only be used with DYNlink safety devices, such as Eden DYN and devices with a Tina adapter.
Description short: Vital 1 Safety controller
Product website: https://new.abb.com/products/ABB2TLA020052R1000
Customs Tariff Number: 85364900
Order Number: 2TLA020052R1000
GTIN-Code: 7350024431810
ECLASS 12.0
27-37-18-19 - Device for monitoring of safety-related circuits:
width: 22.5 mm
Design: Other
height: 84 mm
depth: 120 mm
min. release-delay: 48 - 48 s
max. release-delay: 48 - 48 s
Approval for UL present: false
detachable terminals present: true
Start input present: true
Feedback circuit present: true
Number of outputs, safety-related, non-delayed, with contacts: 2
Number of contacts, safety related, delayed, with contacts: 0
Number of outputs, safety related, non-delayed, semi-conductor: 0
Number of outputs, safety related, delayed, semi-conductor: 0
number of outputs, signaling function, undelayed, with contact: 0
Number of delayed outputs with signaling function (with contact).: 0
Number of undelayed semi-conductor outputs with signaling function: 0
Number of delayed semi-conductor outputs with signaling function.: 0
Design of electrical connection: Screw connection
Bearing track assembly possible: true
min. rated control voltage Us with AC 50 Hz: - - - V
max. rated control supply voltage Us: - - - V
min. rated control voltage Us with AC 60 Hz: - - - V
min. rated control voltage Us with DC: 24 - 24 V
Muting possible: false
Safety type in accordance with IEC 61496-1: 4
Approval for BG BIA present: false
suitable for monitoring solenoid switches: true
suitable for monitoring proximity switches: true
suitable for monitoring EMERGENCY-OFF circuits: true
suitable for monitoring optoelectronic protection devices: true
suitable for monitoring position switches: true
suitable for monitoring tactile sensors: false
suitable for monitoring valves: true
Performance level acc. to EN ISO 13849-1: Level e
Stop Category acc. to IEC 60204: 0
Type of actuation: DC
Design: 1-channel
safety integrity level (SIL): 3
Approval through TÜV present: true
ECLASS 13.0
27-37-18-19 - Device for monitoring of safety-related circuits:
width: 22.5 mm
Design: Other
height: 84 mm
depth: 120 mm
Approval for UL present: false
detachable terminals present: true
Start input present: true
Feedback circuit present: true
Number of outputs, safety-related, non-delayed, with contacts: 2
Number of contacts, safety related, delayed, with contacts: 0
Number of outputs, safety related, non-delayed, semi-conductor: 0
Number of outputs, safety related, delayed, semi-conductor: 0
number of outputs, signaling function, undelayed, with contact: 0
Number of delayed outputs with signaling function (with contact).: 0
Number of undelayed semi-conductor outputs with signaling function: 0
Number of delayed semi-conductor outputs with signaling function.: 0
Design of electrical connection: Screw connection
Bearing track assembly possible: true
Muting possible: false
Safety type in accordance with IEC 61496-1: 4
Approval for BG BIA present: false
suitable for monitoring solenoid switches: true
suitable for monitoring proximity switches: true
suitable for monitoring EMERGENCY-OFF circuits: true
suitable for monitoring optoelectronic protection devices: true
suitable for monitoring position switches: true
suitable for monitoring tactile sensors: false
suitable for monitoring valves: true
Performance level acc. to EN ISO 13849-1: Level e
Stop Category acc. to IEC 60204: 0
Design: 1-channel
safety integrity level (SIL): 3
Approval through TÜV present: true
ECLASS 14.0
27-37-18-19 - Device for monitoring of safety-related circuits:
ETIM 8.0
Device for monitoring of safety-related circuits:
Width: 22.5 mm
Model: Other
Height: 84 mm
Depth: 120 mm
Release-delay: 48 - 48 s
With approval according to UL: false
With detachable clamps: true
With start input: true
With feedback circuit: true
Number of outputs, safety related, undelayed, with contact: 2
Number of outputs, safety related, delayed, with contact: 0
Number of outputs, safety related, undelayed, semiconductors: 0
Number of outputs, safety related, delayed, semiconductors: 0
Number of outputs, signalling function, undelayed, with contact: 0
Number of outputs, signalling function, delayed, with contact: 0
Number of outputs, signalling function, undelayed, semiconductors: 0
Number of outputs, signalling function, delayed, semiconductors: 0
Type of electric connection: Screw connection
Rail mounting possible: true
Rated control supply voltage Us at AC 50HZ: - - - V
Rated control supply voltage Us at AC 60HZ: - - - V
Rated control supply voltage Us at DC: 24 - 24 V
With muting function: false
Type of safety according to IEC 61496-1: 4
With approval for BG BIA: false
Suitable for monitoring of magnetic switches: true
Suitable for monitoring of proximity switches: true
Suitable for monitoring of emergency-stop circuits: true
Suitable for monitoring of optoelectronic protection equipment: true
Suitable for monitoring of position switches: true
Suitable for monitoring of tactile sensors: false
Suitable for monitoring of valves: true
Performance level according to EN ISO 13849-1: Level e
Stop category according to IEC 60204: 0
Voltage type for actuating: DC
Evaluation inputs: 1-channel
SIL according to IEC 61508: 3
With approval for TÜV: true
ETIM 9.0
Device for monitoring of safety-related circuits:
Width: 22.5 mm
Model: Other
Height: 84 mm
Depth: 120 mm
Release-delay: 48 - 48 s
With approval according to UL: false
With detachable clamps: true
With start input: true
With feedback circuit: true
Number of outputs, safety related, undelayed, with contact: 2
Number of outputs, safety related, delayed, with contact: 0
Number of outputs, safety related, undelayed, semiconductors: 0
Number of outputs, safety related, delayed, semiconductors: 0
Number of outputs, signalling function, undelayed, with contact: 0
Number of outputs, signalling function, delayed, with contact: 0
Number of outputs, signalling function, undelayed, semiconductors: 0
Number of outputs, signalling function, delayed, semiconductors: 0
Type of electric connection: Screw connection
Rail mounting possible: true
Rated control supply voltage Us at AC 50HZ: - - - V
Rated control supply voltage Us at AC 60HZ: - - - V
Rated control supply voltage Us at DC: 24 - 24 V
With muting function: false
Type of safety according to IEC 61496-1: 4
With approval for BG BIA: false
Suitable for monitoring of magnetic switches: true
Suitable for monitoring of proximity switches: true
Suitable for monitoring of emergency-stop circuits: true
Suitable for monitoring of optoelectronic protection equipment: true
Suitable for monitoring of position switches: true
Suitable for monitoring of tactile sensors: false
Suitable for monitoring of valves: true
Performance level according to EN ISO 13849-1: Level e
Stop category according to IEC 60204: 0
Voltage type for actuating: DC
Evaluation inputs: 1-channel
SIL according to IEC 61508: 3
With approval for TÜV: true
ETIM 10.0
Device for monitoring of safety-related circuits:
Width: 22.5 mm
Model: Other
Height: 84 mm
Depth: 120 mm
Release-delay: 48 - 48 s
With approval according to UL: false
With detachable clamps: true
With start input: true
With feedback circuit: true
Number of outputs, safety related, undelayed, with contact: 2
Number of outputs, safety related, delayed, with contact: 0
Number of outputs, safety related, undelayed, semiconductors: 0
Number of outputs, safety related, delayed, semiconductors: 0
Number of outputs, signalling function, undelayed, with contact: 0
Number of outputs, signalling function, delayed, with contact: 0
Number of outputs, signalling function, undelayed, semiconductors: 0
Number of outputs, signalling function, delayed, semiconductors: 0
Type of electric connection: Screw connection
Rail mounting possible: true
With muting function: false
Type of safety according to IEC 61496-1: 4
With approval for BG BIA: false
Suitable for monitoring of magnetic switches: true
Suitable for monitoring of proximity switches: true
Suitable for monitoring of emergency-stop circuits: true
Suitable for monitoring of optoelectronic protection equipment: true
Suitable for monitoring of position switches: true
Suitable for monitoring of tactile sensors: false
Suitable for monitoring of valves: true
Performance level according to EN ISO 13849-1: Level e
Stop category according to IEC 60204: 0
Evaluation inputs: 1-channel
SIL according to IEC 61508: 3
With approval for TÜV: true