Catalog navigation
CAD model selection
Selectable products: 3
HELP_VARIABLE
Company
ABB Low Voltage & Systems
Description
HFx-ROL - Electronic Compact Starter
Bill of material
ABB - 1SAT115000R1011 + HF0.6-ROL-24VDC
Product Id
Extended Product Type
Type
HFx-ROL
Description
Electronic Compact Starter, reversing starter with overload protection
Long Description
International product number
Product number of the Manufacturer
Type of motor starter
Reversing starter
With short-circuit release
false
Rated control supply voltage Us at AC 50HZ
0 - 0 V
Rated control supply voltage Us at AC 60HZ
0 - 0 V
Rated control supply voltage Us at DC
24 - 24 V
Rated operation power at AC-3, 230 V, 3-phase
kW
Rated operation power at AC-3, 400 V
kW
Rated operation current Ie
A
Rated operation current at AC-3, 400 V
A
Overload release current setting
A
EFI09603
353.15
Ambient temperature, upper operating limit
80 °C
Temperature compensated overload protection
true
Rail mounting possible
true
With transformer
false
Number of command positions
16
Suitable for emergency stop
false
Number of indicator lights
4
External reset possible
true
With fuse
false
Supporting protocol for TCP/IP
false
Supporting protocol for PROFIBUS
false
Supporting protocol for CAN
false
Supporting protocol for INTERBUS
false
Supporting protocol for ASI
false
Supporting protocol for Modbus
false
Supporting protocol for Data-Highway
false
Supporting protocol for DeviceNet
false
Supporting protocol for SUCONET
false
Supporting protocol for LON
false
Supporting protocol for PROFINET IO
false
Supporting protocol for PROFINET CBA
false
Supporting protocol for SERCOS
false
Supporting protocol for Foundation Fieldbus
false
Supporting protocol for EtherNet/IP
false
Supporting protocol for AS-Interface Safety at Work
false
Supporting protocol for DeviceNet Safety
false
Supporting protocol for INTERBUS-Safety
false
Supporting protocol for PROFIsafe
false
Supporting protocol for SafetyBUS p
false
Supporting protocol for other bus systems
false
Customs tariff number
85371098
Deeplink product page
Link to product detail page
Preview - Generation
Preview
3D
2D

Classifications
CNS
Object Properties:
Manufacturer / brand name: ABB
Customs Tariff Number: 85371098
Description long: The HF-ROL-range is used for forward and reverse running motors, as well as for switching non resistive loads. With contactor and overload relay functionalities integrated into one device, the results are faster wiring times and fewer faults. The range covers 0.6 A, 2.4 A and up to 9 A - for motors up to 3 kW – 500 V AC. The integrated electronic overload protection has a wide setting range that enables just three models to cover all requirements. Setting range of HF0.6-ROL-24VDC is 0.075 A to 0.6 A. The control supply voltage is 24 V DC. For the control and main connection points ABB offers screw connections. ABB also offers a HF-ROLE safety range with emergency stop function. This offers Safety Integrity Level 3, in accordance with functional safety standard IEC 61508-1 and Performance Level 'e' in accordance with ISO 13849-1. The safety range is ATEX-certified.
Description short: HF0.6-ROL-24VDC Electronic Compact Starter
GTIN-Code: 4013614515545
Order Number: 1SAT115000R1011
Product website: Link to product detail page
ETIM 8.0
Motor starter/Motor starter combination:
With transformer: false
Rated operation power at AC-3, 400 V: 0.18 kW
Number of command positions: 16
Suitable for emergency stop: false
Rated operation current Ie: 0.6 A
Number of indicator lights: 4
Overload release current setting: 0.075 - 0.600 A
Supporting protocol for LON: false
Supporting protocol for TCP/IP: false
Supporting protocol for ASI: false
Supporting protocol for PROFIBUS: false
Supporting protocol for CAN: false
Supporting protocol for INTERBUS: false
Supporting protocol for Modbus: false
Supporting protocol for Data-Highway: false
Supporting protocol for DeviceNet: false
Supporting protocol for SUCONET: false
Supporting protocol for other bus systems: false
External reset possible: true
Rail mounting possible: true
Rated control supply voltage Us at AC 50HZ: 0 - 0 V
Rated control supply voltage Us at AC 60HZ: 0 - 0 V
Rated control supply voltage Us at DC: 24 - 24 V
Supporting protocol for SERCOS: false
Supporting protocol for INTERBUS-Safety: false
With short-circuit release: false
With fuse: false
Supporting protocol for AS-Interface Safety at Work: false
Supporting protocol for DeviceNet Safety: false
Supporting protocol for EtherNet/IP: false
Supporting protocol for Foundation Fieldbus: false
Supporting protocol for PROFINET CBA: false
Supporting protocol for PROFINET IO: false
Supporting protocol for PROFIsafe: false
Supporting protocol for SafetyBUS p: false
Type of motor starter: Reversing starter
Rated operation power at AC-3, 230 V, 3-phase: 0.09 kW
Rated operation current at AC-3, 400 V: 0.6 A
Ambient temperature, upper operating limit: 80 °C
Temperature compensated overload protection: true