Catalog navigation
CAD model selection
Selectable products: 1
HELP_VARIABLE
Company
ABB Low Voltage & Systems
Description
MS116 - Manual Motor Starters
Bill of material
ABB - 1SAM250000R1008 + MS116-4.0 Manual Motor Starter Trip class 10A, 2.5 ... 4.0A
Product Id
1SAM250000R1008
Extended Product Type
MS116-4.0
Invoice Description
MS116-4.0 Manual Motor Starter Trip class 10A, 2.5 ... 4.0A
Type
MS116
Description
Manual Motor Starter, Ie = 0.16 ... 16 A
Short Description
MS116-4.0 Manual Motor Starter
Long Description
The MS116-4.0 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 4.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC and trip class 10A. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessory.
International product number
4013614320316
Product number of the Manufacturer
1SAM250000R1008
Manufacturer Name
ABB
Overload release current setting
2.5, 4.0 A
Adjustment range undelayed short-circuit release
50, 50 A
With thermal protection
true
Phase failure sensitive
true
Switch off technique
Thermomagnetic
Rated operating voltage
690, 690 V
Rated permanent current Iu
4 A
Rated operation power at AC-3, 400 V
1.5 kW
Type of electrical connection of main circuit
Screw connection
Type of control element
Turn button
Device construction
Complete device in housing
With integrated auxiliary switch
false
With integrated under voltage release
false
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, AC
75 kA
Degree of protection (IP)
IP20
Height
90 mm
Width
45 mm
Depth
85.6 mm
Customs tariff number
85362010
Deeplink product page
Link to product detail page
Procurement
Last updateJun 17, 2024, 3:41 PM
Part number1SAM250000R1008
AUSSCHREIBEN.DEhttps://qs.ade.adesystem.net/catalog/abb/catalogItem/e67d679c-7671-416b-8f68-49bcc41f7cb3
Currency:
$
£
¥
CN¥
All information without guarantee
Last update: Jun 17, 2024, 3:41 PM
Preview - Generation
Preview
3D
2D
The preview does not represent the part configuration anymore.You have to generate a new preview.

Classifications
CNS
Object Properties:
Order Number: 1SAM250000R1008
Description long: The MS116-4.0 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 4.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC and trip class 10A. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessory.
Description short: MS116-4.0 Manual Motor Starter
Manufacturer / brand name: ABB
Product website: https://new.abb.com/products/ABB1SAM250000R1008
Customs Tariff Number: 85362010
ETIM 8.0
Motor protection circuit-breaker:
Width: 45 mm
Height: 90 mm
Depth: 85.6 mm
Rated operation power at AC-3, 400 V: 1.5 kW
With integrated auxiliary switch: false
Rated permanent current Iu: 4 A
With integrated under voltage release: false
Number of poles: 3
Rated operating voltage: 690, 690 V
Overload release current setting: 2.5, 4.0 A
Degree of protection (IP): IP20
With thermal protection: true
Type of electrical connection of main circuit: Screw connection
Type of control element: Turn button
Switch off technique: Thermomagnetic
Rated short-circuit breaking capacity lcu at 400 V, AC: 75 kA
Adjustment range undelayed short-circuit release: 50, 50 A
Phase failure sensitive: true
Device construction: Complete device in housing